Fairfax County, VA, excluding the incorporated towns, which run their own zoning.
“data center” is Zonescore's word, not the ordinance's. This ordinance never uses it. The term it uses is Data Center, and that is the term cited and quoted below. We matched them because the ordinance defines Data Center as:
A facility containing one or more large-scale computer systems used for data storage and processing for off-site users.
Sec. 9103.6.A -- Data Center
| District | Properties loaded | Code | What says so |
|---|---|---|---|
| C-3 Varies Depends: by right if the use meets the use standards in Sec. 4102.6.A, otherwise special exception; by right, only if the use is a type or location that Sec. 4102.6.A(5) allows here and the use stays within the limits in Sec. 4102.6.A(2); this table cell allows the use in more than one way (by right or special exception), and the use standards in Sec. 4102.6.A set which way applies the use table's own cell Sec. 4102.6.A, Sec. 4102.6.A(5), Sec. 4102.6.A(2): (5) A data center building must be located at least one mile from a Metro station entrance. A lesser distance may be allowed with special exception approval in accordance with subsection 8100.3. … A data center building must be located at least one mile from a Metro station entrance. A lesser distance may be allowed with special exception approval in accordance with subsection 8100.3. … In the C-3 and C-4 Districts, the maximum building size is 40,000 square feet of gross floor area. However, this size limit may be exceeded with special exception approval in accordance with subsection 8100.3. | 730 no ZIP in the county's record (45), 20121 (3), 20170 (1), 20171 (3), 20191 (3), 22003 (286), 22030 (2), 22031 (71), 22033 (2), 22041 (4), 22042 (45), 22043 (98), 22044 (6), 22046 (1), 22079 (1), 22101 (10), 22102 (16), 22150 (8), 22182 (77), 22302 (1), 22303 (2), 22306 (1), 22307 (4), 22309 (1), 22310 (30), 22312 (9) | P/SE | Sec. 4101 Read from the use table: Table 4101.1, row "Data Center", column "C-3", reads "P/SE". Sec. 4101.1 says: I. If a cell in Table 4101.1 or Table 4101.2 contains more than one approval type, there is more than one possible way to establish the use, as referenced in the related use standards for the specific use. For example, when a cell contains a “P” as well as an “SE” or “SP,” if the use does not meet the standards when permitted by right, it may be established with BZA or Board approval in accordance with the applicable special exception or special permit standards and procedures. |
| C-3 (same district) when the use meets the use standards in Sec. 4102.6.A | 730 no ZIP in the county's record (45), 20121 (3), 20170 (1), 20171 (3), 20191 (3), 22003 (286), 22030 (2), 22031 (71), 22033 (2), 22041 (4), 22042 (45), 22043 (98), 22044 (6), 22046 (1), 22079 (1), 22101 (10), 22102 (16), 22150 (8), 22182 (77), 22302 (1), 22303 (2), 22306 (1), 22307 (4), 22309 (1), 22310 (30), 22312 (9) | P | Sec. 4102.6.A (5) A data center building must be located at least one mile from a Metro station entrance. A lesser distance may be allowed with special exception approval in accordance with subsection 8100.3. |
| C-3 (same district) when the use does not meet the use standards in Sec. 4102.6.A | 730 no ZIP in the county's record (45), 20121 (3), 20170 (1), 20171 (3), 20191 (3), 22003 (286), 22030 (2), 22031 (71), 22033 (2), 22041 (4), 22042 (45), 22043 (98), 22044 (6), 22046 (1), 22079 (1), 22101 (10), 22102 (16), 22150 (8), 22182 (77), 22302 (1), 22303 (2), 22306 (1), 22307 (4), 22309 (1), 22310 (30), 22312 (9) | SE | Sec. 4101 If a cell in Table 4101.1 or Table 4101.2 contains more than one approval type, there is more than one possible way to establish the use, as referenced in the related use standards for the specific use. |
| C-4 Varies Depends: by right if the use meets the use standards in Sec. 4102.6.A, otherwise special exception; by right, only if the use is a type or location that Sec. 4102.6.A(5) allows here and the use stays within the limits in Sec. 4102.6.A(2); this table cell allows the use in more than one way (by right or special exception), and the use standards in Sec. 4102.6.A set which way applies the use table's own cell Sec. 4102.6.A, Sec. 4102.6.A(5), Sec. 4102.6.A(2): (5) A data center building must be located at least one mile from a Metro station entrance. A lesser distance may be allowed with special exception approval in accordance with subsection 8100.3. … A data center building must be located at least one mile from a Metro station entrance. A lesser distance may be allowed with special exception approval in accordance with subsection 8100.3. … In the C-3 and C-4 Districts, the maximum building size is 40,000 square feet of gross floor area. However, this size limit may be exceeded with special exception approval in accordance with subsection 8100.3. | 73 no ZIP in the county's record (13), 22003 (1), 22030 (19), 22041 (2), 22042 (3), 22043 (1), 22102 (21), 22150 (5), 22182 (8) | P/SE | Sec. 4101 Read from the use table: Table 4101.1, row "Data Center", column "C-4", reads "P/SE". Sec. 4101.1 says: I. If a cell in Table 4101.1 or Table 4101.2 contains more than one approval type, there is more than one possible way to establish the use, as referenced in the related use standards for the specific use. For example, when a cell contains a “P” as well as an “SE” or “SP,” if the use does not meet the standards when permitted by right, it may be established with BZA or Board approval in accordance with the applicable special exception or special permit standards and procedures. |
| C-4 (same district) when the use meets the use standards in Sec. 4102.6.A | 73 no ZIP in the county's record (13), 22003 (1), 22030 (19), 22041 (2), 22042 (3), 22043 (1), 22102 (21), 22150 (5), 22182 (8) | P | Sec. 4102.6.A (5) A data center building must be located at least one mile from a Metro station entrance. A lesser distance may be allowed with special exception approval in accordance with subsection 8100.3. |
| C-4 (same district) when the use does not meet the use standards in Sec. 4102.6.A | 73 no ZIP in the county's record (13), 22003 (1), 22030 (19), 22041 (2), 22042 (3), 22043 (1), 22102 (21), 22150 (5), 22182 (8) | SE | Sec. 4101 If a cell in Table 4101.1 or Table 4101.2 contains more than one approval type, there is more than one possible way to establish the use, as referenced in the related use standards for the specific use. |
| I-2 Varies Depends: by right if the use meets the use standards in Sec. 4102.6.A, otherwise special exception; by right, only if the use is a type or location that Sec. 4102.6.A(5) allows here and the use stays within the limits in Sec. 4102.6.A(3); this table cell allows the use in more than one way (by right or special exception), and the use standards in Sec. 4102.6.A set which way applies the use table's own cell Sec. 4102.6.A, Sec. 4102.6.A(5), Sec. 4102.6.A(3): (5) A data center building must be located at least one mile from a Metro station entrance. A lesser distance may be allowed with special exception approval in accordance with subsection 8100.3. … A data center building must be located at least one mile from a Metro station entrance. A lesser distance may be allowed with special exception approval in accordance with subsection 8100.3. … In the I-2, I-3, and I-4 Districts, the maximum building size is 80,000 square feet of gross floor area. However, this size limit may be exceeded with special exception approval in accordance with subsection 8100.3. | 5 no ZIP in the county's record (2), 20171 (1), 20191 (2) | P/SE | Sec. 4101 Read from the use table: Table 4101.1, row "Data Center", column "I-2", reads "P/SE". Sec. 4101.1 says: I. If a cell in Table 4101.1 or Table 4101.2 contains more than one approval type, there is more than one possible way to establish the use, as referenced in the related use standards for the specific use. For example, when a cell contains a “P” as well as an “SE” or “SP,” if the use does not meet the standards when permitted by right, it may be established with BZA or Board approval in accordance with the applicable special exception or special permit standards and procedures. |
| I-2 (same district) when the use meets the use standards in Sec. 4102.6.A | 5 no ZIP in the county's record (2), 20171 (1), 20191 (2) | P | Sec. 4102.6.A (5) A data center building must be located at least one mile from a Metro station entrance. A lesser distance may be allowed with special exception approval in accordance with subsection 8100.3. |
| I-2 (same district) when the use does not meet the use standards in Sec. 4102.6.A | 5 no ZIP in the county's record (2), 20171 (1), 20191 (2) | SE | Sec. 4101 If a cell in Table 4101.1 or Table 4101.2 contains more than one approval type, there is more than one possible way to establish the use, as referenced in the related use standards for the specific use. |
| I-3 Varies Depends: by right if the use meets the use standards in Sec. 4102.6.A, otherwise special exception; by right, only if the use is a type or location that Sec. 4102.6.A(5) allows here and the use stays within the limits in Sec. 4102.6.A(3); this table cell allows the use in more than one way (by right or special exception), and the use standards in Sec. 4102.6.A set which way applies the use table's own cell Sec. 4102.6.A, Sec. 4102.6.A(5), Sec. 4102.6.A(3): (5) A data center building must be located at least one mile from a Metro station entrance. A lesser distance may be allowed with special exception approval in accordance with subsection 8100.3. … A data center building must be located at least one mile from a Metro station entrance. A lesser distance may be allowed with special exception approval in accordance with subsection 8100.3. … In the I-2, I-3, and I-4 Districts, the maximum building size is 80,000 square feet of gross floor area. However, this size limit may be exceeded with special exception approval in accordance with subsection 8100.3. | 274 no ZIP in the county's record (26), 20151 (131), 20190 (5), 20191 (75), 22015 (2), 22041 (2), 22042 (2), 22102 (22), 22150 (7), 22182 (2) | P/SE | Sec. 4101 Read from the use table: Table 4101.1, row "Data Center", column "I-3", reads "P/SE". Sec. 4101.1 says: I. If a cell in Table 4101.1 or Table 4101.2 contains more than one approval type, there is more than one possible way to establish the use, as referenced in the related use standards for the specific use. For example, when a cell contains a “P” as well as an “SE” or “SP,” if the use does not meet the standards when permitted by right, it may be established with BZA or Board approval in accordance with the applicable special exception or special permit standards and procedures. |
| I-3 (same district) when the use meets the use standards in Sec. 4102.6.A | 274 no ZIP in the county's record (26), 20151 (131), 20190 (5), 20191 (75), 22015 (2), 22041 (2), 22042 (2), 22102 (22), 22150 (7), 22182 (2) | P | Sec. 4102.6.A (5) A data center building must be located at least one mile from a Metro station entrance. A lesser distance may be allowed with special exception approval in accordance with subsection 8100.3. |
| I-3 (same district) when the use does not meet the use standards in Sec. 4102.6.A | 274 no ZIP in the county's record (26), 20151 (131), 20190 (5), 20191 (75), 22015 (2), 22041 (2), 22042 (2), 22102 (22), 22150 (7), 22182 (2) | SE | Sec. 4101 If a cell in Table 4101.1 or Table 4101.2 contains more than one approval type, there is more than one possible way to establish the use, as referenced in the related use standards for the specific use. |
| I-4 Varies Depends: by right if the use meets the use standards in Sec. 4102.6.A, otherwise special exception; by right, only if the use is a type or location that Sec. 4102.6.A(5) allows here and the use stays within the limits in Sec. 4102.6.A(3); this table cell allows the use in more than one way (by right or special exception), and the use standards in Sec. 4102.6.A set which way applies the use table's own cell Sec. 4102.6.A, Sec. 4102.6.A(5), Sec. 4102.6.A(3): (5) A data center building must be located at least one mile from a Metro station entrance. A lesser distance may be allowed with special exception approval in accordance with subsection 8100.3. … A data center building must be located at least one mile from a Metro station entrance. A lesser distance may be allowed with special exception approval in accordance with subsection 8100.3. … In the I-2, I-3, and I-4 Districts, the maximum building size is 80,000 square feet of gross floor area. However, this size limit may be exceeded with special exception approval in accordance with subsection 8100.3. | 475 no ZIP in the county's record (38), 20151 (108), 20170 (2), 20171 (16), 20190 (14), 20191 (55), 20196 (1), 22030 (3), 22031 (40), 22042 (3), 22043 (1), 22079 (65), 22102 (3), 22150 (5), 22151 (11), 22152 (6), 22160 (1), 22182 (83), 22310 (13), 22312 (3), 22315 (4) | P/SE | Sec. 4101 Read from the use table: Table 4101.1, row "Data Center", column "I-4", reads "P/SE". Sec. 4101.1 says: I. If a cell in Table 4101.1 or Table 4101.2 contains more than one approval type, there is more than one possible way to establish the use, as referenced in the related use standards for the specific use. For example, when a cell contains a “P” as well as an “SE” or “SP,” if the use does not meet the standards when permitted by right, it may be established with BZA or Board approval in accordance with the applicable special exception or special permit standards and procedures. |
| I-4 (same district) when the use meets the use standards in Sec. 4102.6.A | 475 no ZIP in the county's record (38), 20151 (108), 20170 (2), 20171 (16), 20190 (14), 20191 (55), 20196 (1), 22030 (3), 22031 (40), 22042 (3), 22043 (1), 22079 (65), 22102 (3), 22150 (5), 22151 (11), 22152 (6), 22160 (1), 22182 (83), 22310 (13), 22312 (3), 22315 (4) | P | Sec. 4102.6.A (5) A data center building must be located at least one mile from a Metro station entrance. A lesser distance may be allowed with special exception approval in accordance with subsection 8100.3. |
| I-4 (same district) when the use does not meet the use standards in Sec. 4102.6.A | 475 no ZIP in the county's record (38), 20151 (108), 20170 (2), 20171 (16), 20190 (14), 20191 (55), 20196 (1), 22030 (3), 22031 (40), 22042 (3), 22043 (1), 22079 (65), 22102 (3), 22150 (5), 22151 (11), 22152 (6), 22160 (1), 22182 (83), 22310 (13), 22312 (3), 22315 (4) | SE | Sec. 4101 If a cell in Table 4101.1 or Table 4101.2 contains more than one approval type, there is more than one possible way to establish the use, as referenced in the related use standards for the specific use. |
| I-5 Varies Depends: by right if the use meets the use standards in Sec. 4102.6.A, otherwise special exception; by right, only if the use is a type or location that Sec. 4102.6.A(5) allows here; this table cell allows the use in more than one way (by right or special exception), and the use standards in Sec. 4102.6.A set which way applies the use table's own cell Sec. 4102.6.A, Sec. 4102.6.A(5): (5) A data center building must be located at least one mile from a Metro station entrance. A lesser distance may be allowed with special exception approval in accordance with subsection 8100.3. … A data center building must be located at least one mile from a Metro station entrance. A lesser distance may be allowed with special exception approval in accordance with subsection 8100.3. | 1,876 no ZIP in the county's record (147), 20121 (142), 20151 (423), 20153 (1), 20171 (58), 20190 (67), 20191 (3), 22015 (28), 22030 (54), 22031 (134), 22032 (4), 22039 (4), 22042 (29), 22043 (23), 22046 (4), 22079 (214), 22082 (1), 22102 (35), 22150 (61), 22151 (63), 22153 (177), 22161 (1), 22180 (2), 22182 (47), 22303 (2), 22310 (36), 22312 (116) | P/SE | Sec. 4101 Read from the use table: Table 4101.1, row "Data Center", column "I-5", reads "P/SE". Sec. 4101.1 says: I. If a cell in Table 4101.1 or Table 4101.2 contains more than one approval type, there is more than one possible way to establish the use, as referenced in the related use standards for the specific use. For example, when a cell contains a “P” as well as an “SE” or “SP,” if the use does not meet the standards when permitted by right, it may be established with BZA or Board approval in accordance with the applicable special exception or special permit standards and procedures. |
| I-5 (same district) when the use meets the use standards in Sec. 4102.6.A | 1,876 no ZIP in the county's record (147), 20121 (142), 20151 (423), 20153 (1), 20171 (58), 20190 (67), 20191 (3), 22015 (28), 22030 (54), 22031 (134), 22032 (4), 22039 (4), 22042 (29), 22043 (23), 22046 (4), 22079 (214), 22082 (1), 22102 (35), 22150 (61), 22151 (63), 22153 (177), 22161 (1), 22180 (2), 22182 (47), 22303 (2), 22310 (36), 22312 (116) | P | Sec. 4102.6.A (5) A data center building must be located at least one mile from a Metro station entrance. A lesser distance may be allowed with special exception approval in accordance with subsection 8100.3. |
| I-5 (same district) when the use does not meet the use standards in Sec. 4102.6.A | 1,876 no ZIP in the county's record (147), 20121 (142), 20151 (423), 20153 (1), 20171 (58), 20190 (67), 20191 (3), 22015 (28), 22030 (54), 22031 (134), 22032 (4), 22039 (4), 22042 (29), 22043 (23), 22046 (4), 22079 (214), 22082 (1), 22102 (35), 22150 (61), 22151 (63), 22153 (177), 22161 (1), 22180 (2), 22182 (47), 22303 (2), 22310 (36), 22312 (116) | SE | Sec. 4101 If a cell in Table 4101.1 or Table 4101.2 contains more than one approval type, there is more than one possible way to establish the use, as referenced in the related use standards for the specific use. |
| I-6 Varies Depends: by right if the use meets the use standards in Sec. 4102.6.A, otherwise special exception; by right, only if the use is a type or location that Sec. 4102.6.A(5) allows here; this table cell allows the use in more than one way (by right or special exception), and the use standards in Sec. 4102.6.A set which way applies the use table's own cell Sec. 4102.6.A, Sec. 4102.6.A(5): (5) A data center building must be located at least one mile from a Metro station entrance. A lesser distance may be allowed with special exception approval in accordance with subsection 8100.3. … A data center building must be located at least one mile from a Metro station entrance. A lesser distance may be allowed with special exception approval in accordance with subsection 8100.3. | 187 no ZIP in the county's record (31), 20120 (3), 20151 (1), 22015 (1), 22046 (2), 22079 (104), 22150 (2), 22151 (23), 22159 (1), 22304 (7), 22312 (12) | P/SE | Sec. 4101 Read from the use table: Table 4101.1, row "Data Center", column "I-6", reads "P/SE". Sec. 4101.1 says: I. If a cell in Table 4101.1 or Table 4101.2 contains more than one approval type, there is more than one possible way to establish the use, as referenced in the related use standards for the specific use. For example, when a cell contains a “P” as well as an “SE” or “SP,” if the use does not meet the standards when permitted by right, it may be established with BZA or Board approval in accordance with the applicable special exception or special permit standards and procedures. |
| I-6 (same district) when the use meets the use standards in Sec. 4102.6.A | 187 no ZIP in the county's record (31), 20120 (3), 20151 (1), 22015 (1), 22046 (2), 22079 (104), 22150 (2), 22151 (23), 22159 (1), 22304 (7), 22312 (12) | P | Sec. 4102.6.A (5) A data center building must be located at least one mile from a Metro station entrance. A lesser distance may be allowed with special exception approval in accordance with subsection 8100.3. |
| I-6 (same district) when the use does not meet the use standards in Sec. 4102.6.A | 187 no ZIP in the county's record (31), 20120 (3), 20151 (1), 22015 (1), 22046 (2), 22079 (104), 22150 (2), 22151 (23), 22159 (1), 22304 (7), 22312 (12) | SE | Sec. 4101 If a cell in Table 4101.1 or Table 4101.2 contains more than one approval type, there is more than one possible way to establish the use, as referenced in the related use standards for the specific use. |
These require a hearing or an approval from the county. They are not a “no”, and they are not a “yes” either.
| District | Properties loaded | Code | What says so |
|---|---|---|---|
| PDC / Principal the use table's own cell | no parcels loaded | SE | Sec. 4101 Read from the use table: Table 4101.2, row "Data Center", column "PDC / Principal", reads "SE". Sec. 4101.1 says: D. An “SE” in a cell of Table 4101.1 or Table 4101.2 indicates that the use can be established only with Board approval of a special exception in accordance with subsection 8101.3 and related use standards. |
| PTC the use table's own cell | 533 no ZIP in the county's record (67), 22102 (432), 22182 (34) | SE | Sec. 4101 Read from the use table: Table 4101.2, row "Data Center", column "PTC", reads "SE". Sec. 4101.1 says: D. An “SE” in a cell of Table 4101.1 or Table 4101.2 indicates that the use can be established only with Board approval of a special exception in accordance with subsection 8101.3 and related use standards. |
Pro and reports for Fairfax County, VA are coming soon.
We use this email only to tell you when Fairfax County, VA launches. We never share it.
This answer is good through July 1, 2026 — that is the date the ordinance we hold runs to, as published by Fairfax County. We last checked with the county on September 14, 2026 and found nothing newer. That is a check on that date, not a promise about today.
(none) above means a parcel we could not place inside any zoning district on the county's zoning map — 1,697 of them. We hold no zone on the parcel record we fetch from the county, so this is our reading of its map rather than a blank in its data.Sale history and assessed values from Fairfax County Department of Tax Administration records, retrieved October 5, 2026.
Built from scripts/build_reverse_index.py, generated 2026-10-11T20:59:04+00:00.